Installation, Operation and Maintenance1.5 Through 5 Ton Split System Air ConditionerINTRODUCTION...
INTRODUCTIONYou have made a major investment in a fine piece ofequipment. Keep your investment sound by reading theseinstructions before installing th
2Six feetclearanceabove theunitThree feetclearance Rain GuttersConcrete slabor preformed padThree feetclearance INSTALLATIONCondensing Unit LocationTh
SERVICE VALVE CONNECTIONSBraze joints1. Remove the valve core from the schrader port. Wrap aquenching cloth around the service valve. Clean and fluxth
4CONNECT REFRIGERANT PIPINGThe following guidelines should be followed when installingrefrigerant piping. Comply with all local, state, and federalcod
1. If the furnace and air conditioner are on separatethermostats, turn the furnace thermostat off during thecooling season to prevent simultaneous ope
624AB1 VF DC18 = 18000 BTU/H [5.28 kW]24 = 24000 BTU/H [7.03 kW]30 = 30000 BTU/H [8.79 kW]36 = 36000 BTU/H [10.55 kW]42 = 42000 BTU/H [12.31 kW]48 =
Model C10 &THIS WARRANTY DOES NOT COVER DAMAGE CAUSED BY: •Improper installation •Misuse of equipment • Negligent servicing • Improper applicatio